Description of changes contained in version 2_98 (6/29/2011) Fixed RSMINI163 IO port traps going out with wrong trap ID Description of changes contained in version 2_97 (6/7/2011) Added delayed alarms to prevent nuisance notifications Description of changes contained in version V2_96 (3/25/2011) Fixed HTTPS failures introduced in v2_95 Description of changes contained in version V2_95 (3/3/2011) Fixed spurious errors on RTHD, RTAFH and RTAF sensors that could cause them to show up as "Unavailable" or "Unplugged" Better handling of unsupported sensors (DM, IOE, RS2) Updated copyrights to 2011 Description of changes contained in version V2_94 (8/12/2010) Added support for new RTAFHD3 sensors Fixed a potential lockup on bootup Temperature logging range changed to -40C/F to +123C/253F Note: All temperature logs will be rescaled after updating to this firmware. Please download and save your log history prior to updating if you wish to maintain it. Description of changes contained in version V2_93 (5/26/2010) Improved CCAT reliability Added ability to reset HTTP port via Telnet Description of changes contained in version V2_92 (3/15/2010) Fixed an issue introduced in V2_91 that could cause units to become unresponsive Added support for all Axis and Linksys webcams Improved SNMP sysObjectID conformance with RFC 1213 Fixed RSMINI163 IO port data reporting as Humidity, Airflow and Light in SNMP Improved communication reliability with CCAT sensors Air Speed Switch sensor names made consistent with RacSense v3 Description of changes contained in version V2_91 (2/18/2010) Added support for new airspeed sensor SSL certificate now uses SHA-1 instead of MD5 I/O sensor friendly names with special characters are now handled properly in the XML file Description of changes contained in version V2_88 (12/4/2009) Fixed a security hole that could allow changes to a unit's configuration without requiring a password Added support for D-Link DCS-920 camera Description of changes contained in version V2_87 (11/5/2009) Improved communications with RTAFH and RTHD sensors Added a checkbox on the Alarms page to stop nuisance sensor unplugged alarms Added support for most D-Link cameras Added support for most Axis cameras Fixed a potential false alarm when using a temperature offset Description of changes contained in version V2_86 (6/17/2009) Fixed an issue with XML on RFC units Improved Power On Action behavior on RCM-O reboot Emails now send current IP address when using DHCP Config page shows current network information when using DHCP Fixed spurious alarms on RSS Fixed sensors showing up unplugged after one bad reading Description of changes contained in version V2_84 (2/25/2009) Added support for D-Link DCS-3410 and DCS-910 Minor modifications to Alarms page Improved RCM-O compatibility with Console Added support for SNMP Sets on sysLocation, sysName and sysContact Website footer syncs with SNMP sysLocation, sysName and sysContact MIB information is now more consistent across units SNMP now reports all amps values in deciamps (0.1 amps) Note: This will likely trigger alarms on systems set to monitor amps until those systems have their thresholds adjusted. For example, 4.2 amps was previously reported as "4" and is now reported as "42". Description of changes contained in version V2_82 (11/24/2008) Changed default time servers to time.nist.gov and time-a.nist.gov Kilowatt-hours no longer shows up on Logs page graphs Minor XML changes for RCM, RCM-O and RCU Fixed a bug involving '\' characters in friendly names Fixed minor issues with SNMP GET and GETNEXT Added more data to MIB for RCM-O Alarm emails now report sensor friendly name Increased accuracy of RSP when running on 50Hz power Added alarm scrolling capability to units with LCD displays To enable, check the box on the Alarms page. LCD will display "Warming Up" for approximately 3 minutes before scrolling begins to allow values to settle down. Description of changes contained in version V2_80 (10/6/2008) Added support for new RCM-O product Improved SMTP compatibility Increased SNMP variable binding limit to 32 (was 10) Improved RCM/RCU relay error reporting Moved RCM/RCU control to new page Added "Restore Defaults" button for RCM and RCU outlet settings Fixed potential errors in XML page Improved accuracy of RSP Fixed errant "Unplugged" issue with RSS Description of changes contained in version V2_78 (5/5/2008) Improved compatibility with Apache proxy Updated copyright to 2003-8 Friendly names containing ‘,’ and ‘ “ ‘ now display properly Improved CSV file compatibility with Excel Decreased relay error reporting time on RCM/RCU Fixed “address-backup” attribute on XML page showing wrong IP address Added “Select Group” checkbox to RCM/RCU control page Added support for Panasonic IP-enabled webcams Fixed a possible infinite loop in SSL caused by partial packets Removed unused SNMP Read/Write Community field on config page Fixed RCM/RCU feedback errors in SNMP Fixed issue where high light levels caused internal sensors to stop responding on RSM and RSE Description of changes contained in version V2_77 (2/29/2008) Fixed graph lines go below the border of the graph when data is negative Added support for DCS-5300/5300G firmwares 1.02 and 1.05 Added support for DSC-3420 Changed "TruthValue" entries to be type "Unsigned32" for v1 SNMP Updater instructions have been modified Fixed RSP and RSS test SNMP traps Description of changes contained in version V2_76 (2/1/2008) Added sensor types for City Power Monitor, Smoke Alarm, -48Vdc sensor and 30Vdc sensor Added support for ESMTP AUTH to e-mail system Revamped SNMP support with major speed and stability improvements Please note that SNMPv2 support was disabled in this release. Be sure to import the new MIB into your SNMP package and set it to use SNMPv1 when contacting Racsense units. Fixed WAP page incompatibility with some mobile browsers Fixed Dewpoint readings show up on Temperature readings graph in Console Description of changes contained in version V2_75 (1/9/2008) Added “Unit Description” field to Config page and footer Fixed bug introduced in 2.74 where external sensors did not always show up in SNMP Disabled log storage capability on RSP due to data corruption Fixed HTTPS not working Description of changes contained in version V2_74 (11/21/2007) Added support for Linksys WVC200 webcam Added alarm trip status to XML page Added productHardware OID to SNMP tree Added sensorCounts table to SNMP tree Removed group amps entry on RCM units Description of changes contained in version V2_72 (10/9/2007) Added log storage capability to RSP Fixed RSM remote temperature sensors read 0C/32F bug Fixed remote temperature sensor graphs showing negative values when temperature >50C Set new limits on all temperature values: Min: -20C Max: 50C Description of changes contained in version V2_70 (9/17/2007) Added current sensor values to graph legend on Logs page Added support for D-Link DCS-2000 Added support for "Digital" CCAT Added device friendly name to browser title bar Added Celsius/Fahrenheit option to Fan Controller and RCM/RCU Fixed WAP page password protection Internal temperature offset enabled on Fan Controller Now allows 0.0.0.0 for DNS IP Description of changes contained in version V2_65 (6/25/2007) Added support for new dew point sensor Fixed NTP sever switches between primary/secondary addresses on NTP server timeout Fixed temp sensor when appeared unplugged near 0 deg. C Fixed name for RSS "Satellite" Added support for D-Link DCS-3220 Added alarm test on Alarms page for all units Fixed sensor friendly name and product friendly name added to MIB TRAP variable bindings Fixed incorrect sensor friendly name OID in SNMP trap Added alarmTripType variable added to MIB and SNMP traps Description of changes contained in version V2_63 (2/12/2007) Fixed DNS applies to NTP Added support for updater with unidentified device Fixed group amps reporting on RCM/RCU products Description of changes contained in version V2_62 (11/15/2006) Added support for DNS names in SMTP, POP3, SNMP, and NTP server names Added PDA control page for RCM/RCU Added support for D-Link DCS-6620 camera Added telnet command "uptime", displays elapsed time since last reboot Added telnet command "datalog", dump sensor log data for debugging Alarm emails now display most useful information first for devices that truncate emails Added device administration information now included in status report and alarm emails Fixed adding in missing imports from MIB Fixed user specified internal temperature offset on some units Fixed alarm buzzer not an option on RSMINI163, RSMINI Fixed telnet, no longer allows arbitrary number of simultaneous connections Fixed telnet, device checksum not being displayed in "report" command Removed "HTML v4.0.1 Verified" image from webpage, it gave spurious error message on certian browsers when using HTTP/SSL Fixed RSM I/O, I/O ports 1 and 3 were swapped in a previous version Description of changes contained in version V2_60 (8/20/2006) Fix range of AFHT sensor values to 0,99 from 1,99 Image retrieval patch for DCS 5300/5300G camera with firmware v1.03 Fix set allarm ranges on RCM Description of changes contained in version V2_59 Fix for RSMINI/RSMINI163 being recognized as RSE Added support for up to 4 cameras on a single unit Added support for D-Link DCS-5300/5300G camera Corrected HTML/XML error with special characters in friendly names Added support for up to 16 RTAFH sensors Corrected Read-only username error Corrected buffer over-run in event time-stamp logger Removed special "(None)" FTP account Corrected occasional "{nil}" displayed as the name of the unit Fix for email alerts no longer being accepted by SMTP servers. Fix for initial alarm ranges in RCM/RCU being [-10,50]. Description of changes contained in version V2_57d Fix for RSMINI/RSMINI163 being recognized as RSE Added support for up to 4 cameras on a single unit Added support for D-Link DCS-5300/5300G camera Corrected HTML/XML error with special characters in friendly names Added support for up to 16 RTAFH sensors Corrected Read-only username error Corrected buffer over-run in event time-stamp logger Removed special "(None)" FTP account Corrected occasional "{nil}" displayed as the name of the unit Description of changes contained in version V2_55 (4/12/2006) Added SNMP community strings for read-only and read/write access Added OID Tree and MIB to installer file Added additional support for browsers that don't support the