Vertiv Geist rPDU
 

VP7N21A2

Part #: VP7N21A2
Model Number: 
MNU5M1R5-12CF13-2PS56B0H10-S
Category: 
Switched
Sub Category: 
Outlet Level Monitoring
Power Configuration: 
20A, 240/415V WYE, 11.5kW
Physical Configuration: 
19in / 483mm, Horizontal
Product Summary: 
rPDU, Switched Outlet Level Monitoring EC, 20A, 240/415V WYE, 11.5kW, Horizontal, (12) Combination C13/C19, 10ft / 3m power cord with 3P+N+E (IP44), Black Powder Coat.
Monitoring: 
Input and Outlet power monitoring with Outlet switching. Circuit/Breaker current monitoring. Environmental monitoring via optional remote sensors. Daisy chain Ethernet connectivity. LCD/Touchscreen/Auto-Orientation Display. Secure boot.
Plug Form: 
3P+N+E (IP44)3P+N+E (IP44)
Receptacle: 
Combination C13/C19Combination C13/C19 (Quantity: 12)
Chassis Color Options: 
To discuss color options, contact your local sales representative.

Product Specification and Options

System Features
MonitoringInput and Outlet power monitoring with Outlet switching. Circuit/Breaker current monitoring. Environmental monitoring via optional remote sensors. Daisy chain Ethernet connectivity. LCD/Touchscreen/Auto-Orientation Display. Secure boot.
Input MonitoringTotal Unit Monitoring (kWh, W, VA, PF)
Phase (A, B, C) Monitoring (kWh, W, VA, PF, V, A)

Power Measurements Compliant with ANSI C12.1 and IEC 62053-21 at 1% Accuracy Class Requirements
Circuit MonitoringCircuit / Breaker Monitoring (A)

Circuit/Breaker Current Measurements Independently Tested and Verified at 2% Accuracy
Outlet MonitoringOutlet Monitoring (kWh, W, VA, PF, V, A)

Power Measurements Compliant with ANSI C12.1 and IEC 62053-21 at 1% Accuracy Class Requirements.
Remote Power ManagementIndividual Outlet Switching with Optional User Defined Time Delays and Sequential Power-up
Quantity Of Inputs1
Voltage200-240/346-415V WYE
Current20A x 3 Phase WYE
VA per Input (Load Capacity)11.5kW (240V)
Frequency50/60Hz
Over Current ProtectionNone
SwitchNo
LCD Touchscreen Display / Auto OrientedYes
Indicators - LED(s)12
Power Cable Wire Gauge12/5
Power Cable Length10ft / 3m
Power Entry LocationLeft Rear
Plug TypeIEC60309 3P + N + E, 20A, 230/400V, Splashproof IP44
Receptacle/Socket Type #1Combination C13/C19
- Quantity on Rear12
- Quantity per Phase4
- Circuit Color ID3 Circuit = Orange, Green, Blue
- StyleBanks of 6
- Voltage per Receptacle/Socket240V (L-N)
Network ConnectionDual 10/100/1000Mbps Ethernet
Protocols SupportedDHCP, HTTP, HTTPS, IPv4, IPv6, LDAP, NTP, RADIUS, RSTP, SSH, SMTP, SNMP (v1/v2c/v3), Syslog, TACACS+, Modbus TCP
Data Access FormatsCSV datalog, JSON API, JSON datalog
USB SupportYes
IP Reset ButtonYes
Hard Reboot ButtonYes
Serial ConnectionRS232 via RJ45
Remote Sensor RJ Connection Jacks1 (Supports up to 16 Sensors)
Maximum Operating Temperature60C / 140F
Heavy Steel - Powder Coat FinishBlack
Configuration19in / 483mm Horizontal Rackmount
Adjustable Mount BracketsYes
Country of OriginUSA, TAA Compliant and Buy American Act COTS Compliant
Product Warranty5-year limited warranty if registered within 120 days of purchase, otherwise warranty defaults to 3 years
Certification/Agency ApprovalsRoHS Compliant
Certification/Agency ApprovalsFCC Part 15 Class A Conformance
Certification/Agency ApprovalsUL & c-UL Listed 62368-1
Chassis Dimensions (HxWxD)1.72in x 17in x 12in / 44mm x 432mm x 305mm
Shipped Weight10lbs (4.54kg)