Why do I have an alarm showing tripped even though the current value is below the threshold?

Why do I have an alarm showing tripped even though the current value is below the threshold?

Each alarm has a 1 unit hysteresis built-in to help limit nuisance alarms. This means that a value must change by 1 unit before the alarm will clear. For example, if there is a temperature alarm set with a high trip of 75F, the value must fall below 74F before the alarm will actually clear.